Pipe Guide U-Bolt Shield Guide U-Bolt – G3000

Pipe Guide U-Bolt Shield Guide U-Bolt - G3000 - Details

Request A Quote



General Dimensions & Specifications

Download PDF

Insulation and plate sold separately.

Contact factory for pipe sizes or tube sizes not shown.

Note: For pipe clamps, see: G1000, G1200, G2000, G2200 – For shield clamps, see: G1000 – For shield guide straps, see: G2000.

Easy installation
Sized to provide approximately 1/16″ to 1/8″ radial clearance around O.D. of bare pipe or insulated pipe support models A1000 through A7000
Complete with 4 hex nuts and 4 plain washers
Other sizes available on request

G3000: Applicable PSI specification document: No. 208.
Steel: ASTM A36 1/4 X 1 1/2
Hex Nuts: ASTM A-563 Gr. A
Coating: Primer coating or hot dipped galvanized. Other coatings available upon request.

Formal Submittal Sheets Available

Model G3000 is designed for use on:

  • Cold Water
  • Hot Water
  • Dual Temperature
  • Chilled Water
  • Vacuum
  • Steam
  • Gas
  • Air
Pipe SizeMaximum Lateral Load - lb.Insulation Thickness
ThreadBARE1/2"3/4"1"1 1/2"2"2 1/2"3"4"
ABABABABABABABABDE
1/2501/4 - 201.252.752.53.382.883.633.383.884.54.385.54.887.135.888.136.2510.137.25
3/4501/4 - 201.532.53.382.883.633.383.884.54.385.54.887.135.888.136.2510.137.25
1501/4 - 201.7532.883.633.383.8844.2554.636.255.257.135.888.136.2510.137.25
1 1/4503/8 - 162.253.53.384.133.384.134.134.385.635.136.255.57.2568.256.510.257.5
1 1/2503/8 - 162.53.633.54.134.134.384.634.635.635.137.2568.256.59.25711.258
2503/8 - 162.883.884.134.384.634.635.134.886.255.57.2568.256.59.25711.258
2 1/2501/2 - 133.54.384.884.885.385.135.885.387.56.258.56.759.57.2510.57.7512.58.75
3501/2 - 134.134.635.385.135.885.386.385.637.56.258.56.759.57.2510.57.7512.58.75
3 1/2501/2 - 134.634.885.885.386.385.757.56.258.56.759.58.6310.57.7511.58.2513.59.25
4501/2 - 135.135.136.385.757.56.257.56.258.56.759.58.6310.57.7511.58.2513.59.25
Top