Hardware sold separately. Cross-section & dimension callouts shown in the technical data below.
Insulated 2-Bolt Hanger
D1000
Talk to a pipe support specialist about your application.
1-707-447-5014General Dimensions & Specifications
The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thicknesses.
Contact factory for current information.
| Iron Pipe Size |
Vert. Load (lbs) |
A | B | C | D | Insulation Thickness | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1″ | 2″ | 3″ | 4″ | 5″ | |||||||||||
| E | F | E | F | E | F | E | F | E | F | ||||||
| 1/2 | 65 | 1/8 x 1 1/2 | 0.38 | 0.69 | 0.56 | 2.38 | 4 | 3.44 | 4 | 4.75 | 6 | 5.75 | 6 | 6.81 | 6 |
| 3/4 | 75 | 1/8 x 1 1/2 | 0.38 | 0.69 | 0.56 | 2.38 | 4 | 3.44 | 4 | 4.75 | 6 | 5.75 | 6 | 6.81 | 6 |
| 1 | 90 | 1/8 x 1 1/2 | 0.38 | 0.69 | 0.56 | 2.69 | 4 | 3.72 | 4 | 4.75 | 6 | 5.75 | 6 | 6.81 | 6 |
| 1 1/2 | 150 | 1/8 x 1 1/2 | 0.38 | 0.69 | 0.56 | 2.94 | 4 | 4.25 | 4 | 5.25 | 6 | 6.31 | 6 | 7.31 | 6 |
| 2 | 245 | 1/4 x 1 1/2 | 0.50 | 0.81 | 0.63 | 3.56 | 6 | 4.63 | 6 | 5.63 | 6 | 6.69 | 6 | 7.69 | 6 |
| 2 1/2 | 290 | 1/4 x 1 1/2 | 0.50 | 0.81 | 0.63 | 3.81 | 6 | 5.13 | 6 | 6.13 | 9 | 7.19 | 9 | 8.31 | 9 |
| 3 | 365 | 1/4 x 1 1/2 | 0.63 | 1.06 | 0.63 | 4.22 | 6 | 5.25 | 6 | 6.25 | 9 | 7.31 | 9 | 8.44 | 9 |
| 4 | 475 | 1/4 x 1 1/2 | 0.63 | 1.06 | 0.63 | 4.75 | 6 | 5.75 | 6 | 6.81 | 9 | 7.81 | 9 | 8.94 | 9 |
| TABLE I All dimensions in inches. “A” through “F” refer to the drawing above. | |||||||||||||||
Application
Model D1000 is designed for use on:
- Hot water
- Cold water
- Chilled water
- Dual temperature
- Steam
- Air
- Gas
- Vacuum
Intended to be hung from threaded rod.
Temperature Range
Standard: +40°F to +1200°F CalSil Insulation
Note: Up to 1800°F available upon request.
Cryogenic: -275°F to +275°F Urethane Insulation.
Add U after the model number (i.e., D1000U)
Features
- Compact
- Eliminates welding to pipe
- Copper tubing sizes and pipe sizes
- Minimizes heat loss and/or condensation
- Easy installation
- Overlapping galvanized sheet metal jacket
- Other I.D.’s and/or O.D.’s available on request
Material Data
| D1000 Spec Doc | Applicable PSI spec. doc.: No. 209 |
|---|---|
| Insulation | Calcium silicate, asbestos-free, treated with water repellant |
| Jackets | Galvanized steel, ASTM A-653 |
| Glue | Industrial contact adhesive |
| Steel Straps | Carbon steel, ASTM A-36 |
| Fasteners | ASTM A-307, plated |
| Coating | Primer coated or hot dipped galvanized. Other coatings available upon request. |
| Cryogenic Insulation | Urethane (for -275°F to +275°F service, model D1000U) |
Need a formal submittal?
Formal submittal sheets are available.
Installation Guide
Model A1000 – A4000 & A9000
1. Position the bottom half of the insulated hanger shield (insulating structural material, sheet metal jacket and load plate where applicable) on the pipe at the applicable support location as shown.
2. Hold the top half of the shield firmly. Open the overlapping sheet metal jacket and gently slide into position the top half of the insulated shield over the bottom half shield as shown.
Model A5000 – A8400
1. When used on a flat surface, position shield so that it is centered on the structural steel.
2. When used with a clevis hanger, position shield symmetrically.
3. When models include heat trace groves, the number and location may vary. Check with design drawings for exact number and location. Ensure that the heat tracing cable is properly positioned inside the grove of the shield.
Completed Assembly Without Load Plate
Completed Assembly With Load Plate
Downloads & resources
Custom Design Request
Need other I.D.'s, O.D.'s, temperatures or loads? Submit a custom design request.
Start Request →Revit RFA 3D Model
A1000 Insulated Pipe Support Revit RFA model for BIM & coordination workflows.
Download 3D Model →