Insulated Pipe Support · Regular Duty

A1000

A compact, pre-insulated pipe support that carries hot, cold and chilled lines without welding to the pipe – with an overlapping galvanized jacket that minimizes heat loss and condensation across a wide temperature range.

Load Rating35–2,300 lbs
Pipe Sizes½" – 24" IPS

Talk to a pipe support specialist about your application.

1-707-447-5014

General Dimensions & Specifications

A1000 assembly

Hardware sold separately.
Note: For higher load ratings, see A3000, A9000.
Cross section
Dimension A

Oper.
Temp.
°F
Mult.
Factor
“F”
500 0.90
750 0.75
1000 0.50
1200 0.30
TABLE III
Pipe
Size
MAXIMUM LOAD
RATING (LBS)
On Flat
Surface
(a) (c)
In Clevis
Hanger
(b) (c)
1/2 35 40
3/4 40 45
1 60 65
1 1/4 70 80
1 1/2 100 110
2 125 140
2 1/2 150 200
3 180 250
3 1/2 225 300
4 270 350
5 350 450
6 400 550
8 450 750
10 500 1000
12 550 1200
14 575 1400
16 600 1600
18 625 1800
20 675 2000
24 750 2300
TABLE I
Contact factory for other dimensions,
temperatures, and loads.
Available in all insulation thicknesses.

The load ratings represent average values obtained in accordance with accepted
methods and are subject to normal manufacturing variations. Dimensions and ratings
are subject to change without notice.

a) To develop maximum load rating, width of support surface should be at least 1/2 of dimension “A” in Table II.

b) To develop maximum load rating, use band, ring or clevis hanger with manufacturer’s load rating equal to or greater than values shown in Table I.

c) To obtain load ratings for operating temperatures of 500° F and higher, multiply load rating by factor “F” in Table III.

Iron
Pipe
Size
Insulation Thickness Copper
Tubing
Size O.D.
1/2 3/4 1 1 1/2 2 2 1/2 3 3 1/2 4
A B A B A B A B A B A B A B A B A B
1/2 – 1 1/2 4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24 5/8 – 1 5/8
2 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 2 1/8
2 1/2 – 4 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 2 5/8 – 4 1/8
5 6 20 6 20 6 20 6 20 9 20 9 20 9 20 5 1/8
6 – 7 6 20 6 20 6 20 6 20 9 16 9 16 9 16 6 1/8
8 – 10 9 16 9 16 9 16 9 16 9 16 8 1/8 – 10 1/8
12 – 18 12 16 12 16 12 16 12 16 12 16 12 1/8
20 – 24 18 16 18 16 18 16 18 16 18 16
TABLE II   “B” = gauge of sheet metal jacket

Application

Model A1000 is designed for use on:

  • Hot water
  • Cold water
  • Chilled water
  • Dual temperature
  • Steam
  • Air
  • Gas
  • Vacuum

Intended for installation on:

  • Flat surfaces
  • Band, ring or clevis pipe hanger

Temperature Range

Standard: +40°F to +1200°F CaSi Insulation

Note: Up to 1800°F available upon request.

Cryogenic: -275°F to +275°F Urethane Insulation.

Add U after the model number (i.e., A1000U)

Features

  • Compact
  • Eliminates welding to pipe
  • Minimizes heat loss and/or condensation
  • Other I.D.’s and/or O.D.’s available on request
  • Clevis available (see PTP fig. 83)
  • Easy installation
  • Overlapping galvanized sheet metal jacket
  • Copper tubing sizes available
  • Clamps available (see G-series)
Performance test results on file – available upon request.

Material Data

A1000 Spec Doc Applicable PSI spec. doc.: No. 205
Standard Insulation Calcium silicate, asbestos-free, treated with water repellant
Jackets Galvanized steel, ASTM A-653 (overlapping galvanized
sheet-metal jacket)
Glue Industrial contact adhesive
Cryogenic Insulation Urethane (for -275°F to +275°F service, model A1000U)

Need a formal submittal?

Formal submittal sheets are available.

Request a Quote
Custom Design Request

Installation Guide

Installation Model A1000 - A4000 & A9000

Model A1000 – A4000 & A9000

1. Position the bottom half of the insulated hanger shield (insulating structural material, sheet metal jacket and load plate where applicable) on the pipe at the applicable support location as shown.

2. Hold the top half of the shield firmly. Open the overlapping sheet metal jacket and gently slide into position the top half of the insulated shield over the bottom half shield as shown.

Installation Model A5000 - A8400

Model A5000 – A8400

1. When used on a flat surface, position shield so that it is centered on the structural steel.

2. When used with a clevis hanger, position shield symmetrically.

3. When models include heat trace groves, the number and location may vary. Check with design drawings for exact number and location. Ensure that the heat tracing cable is properly positioned inside the grove of the shield.

Completed assembly without load plate

Completed Assembly Without Load Plate

Completed assembly with load plate

Completed Assembly With Load Plate

Downloads & resources

Form
Custom Design Request

Need other I.D.'s, O.D.'s, temperatures or loads? Submit a custom design request.

Start Request →
RFA
Revit RFA 3D Model

A1000 Insulated Pipe Support Revit RFA model for BIM & coordination workflows.

Download 3D Model →
Meet
Schedule a Meeting

Talk through your application with a Pipe Shields engineer.

Book a Time →
Top