ISO 9001 Certified

Insulated Friction Pipe Anchor

C3300

Load Rating400–18,600 lbs
Pipe Sizes½" – 42" IPS

Talk to a pipe support specialist about your application.

1-707-447-5014

General Dimensions & Specifications


Model C3300 Insulated Friction Pipe Anchor

Base Mounted.
C3300 dimensional drawing

The load ratings represent average values obtained in accordance with accepted
test methods and are subject to normal manufacturing variations. Dimensions and
ratings are subject to change without notice.

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thicknesses.

Note: For higher load ratings, see C4300.

Pipe
Size
Load Rating (lbs) Insulation Thickness
Vert. Lat. Axial 1″ 1 1/2″ 2″ 2 1/2″ 3″ 4″ 5″
B C E B C E B C E B C E B C E B C E B C E
1/2 550 275 110 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
3/4 700 350 140 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 900 450 180 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 1300 650 260 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1500 750 300 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1800 900 360 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
3 2100 1050 420 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 3350 1675 670 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 4200 2100 840 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 5100 2550 1020 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 6800 3400 1360 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 8000 4000 1600 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 8800 4400 1760 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 10000 5000 2000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 11600 5800 2320 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 12800 6400 2560 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 13600 6800 2720 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 14400 7200 2880 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 18800 9400 3760 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 22000 11000 4400 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 24800 12400 4960 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
All dimensions in inches. “B”, “C” and “E” refer to the drawing above.

Application

Model C3300 is designed for use on:

  • Hot water
  • Cold water
  • Chilled water
  • Dual temperature
  • Where thermal cycles are infrequent
  • Steam
  • Air
  • Gas
  • Vacuum
  • Where axial forces are relatively light or in balance

Intended for installation on:

  • Flat surfaces

Temperature Range

Standard: +40°F to +1200°F CalSil Insulation

Note: Up to 1800°F available upon request.

Cryogenic: -275°F to +275°F Urethane Insulation.

Add U after the model number (i.e., C3300U)

Features

  • All pipe sizes
  • Eliminates welding to pipe
  • Insulating structural inserts for load transfer
  • Bottom-of-pipe to top-of-steel matches insulated supports in “B” series
  • Easy installation
  • Overlapping galvanized sheet metal jacket
  • Other I.D.’s and/or O.D.’s available on request
Performance test results on file – available upon request.

Material Data

C3300 Spec Doc Applicable PSI spec. doc.: No. 209
Insulation Calcium silicate, asbestos-free, treated with water repellant
Jackets Galvanized steel, ASTM A-653
Glue Industrial contact adhesive
Structural Inserts High-density calcium silicate, asbestos-free, treated with water repellant
Steel Straps / Base Carbon steel, ASTM A-36
Fasteners ASTM A-307, plated
Coating Primer coated or hot dipped galvanized. Other coatings available upon request.
Cryogenic Insulation Urethane (for -275°F to +275°F service, model C3300U)

Need a formal submittal?

Formal submittal sheets are available.

Request a Quote
Custom Design Request

Installation Guide

Installation Model A1000 - A4000 & A9000

Model A1000 – A4000 & A9000

1. Position the bottom half of the insulated hanger shield (insulating structural material, sheet metal jacket and load plate where applicable) on the pipe at the applicable support location as shown.

2. Hold the top half of the shield firmly. Open the overlapping sheet metal jacket and gently slide into position the top half of the insulated shield over the bottom half shield as shown.

Installation Model A5000 - A8400

Model A5000 – A8400

1. When used on a flat surface, position shield so that it is centered on the structural steel.

2. When used with a clevis hanger, position shield symmetrically.

3. When models include heat trace groves, the number and location may vary. Check with design drawings for exact number and location. Ensure that the heat tracing cable is properly positioned inside the grove of the shield.

Completed assembly without load plate

Completed Assembly Without Load Plate

Completed assembly with load plate

Completed Assembly With Load Plate

Downloads & resources

Form
Custom Design Request

Need other I.D.'s, O.D.'s, temperatures or loads? Submit a custom design request.

Start Request →
RFA
Revit RFA 3D Model

A1000 Insulated Pipe Support Revit RFA model for BIM & coordination workflows.

Download 3D Model →
Meet
Schedule a Meeting

Talk through your application with a Pipe Shields engineer.

Book a Time →
Top