Hardware Sold Separately – Note: For higher load ratings, see A8400, B1100. The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice.
Compact
Easy Installation
Eliminates welding to pipe
Overlapping galvanized sheet metal jacket
Insulating structural inserts for load transfer
Minimizes heat loss and/or condensation
Load distribution plate integral with bottom jacket
Copper tubing sizes available
Other I.D.’s and/or O.D.’s available on request
Performance Test Results on File: Available upon request.
A8200: Applicable PSI spec. doc.: No. 205
Insulation: Calcium Silicate asbestos-free, treated with water repellant.
Jackets: Galvanized Steel ASTMA-527
Structural Inserts: High-density calcium silicate asbestos-free, treated with water repellant.
Load Distribution Plate: Carbon Steel ASTM A-36
Coating: Primer coated or hot-dip galvanized. Other coatings available upon request.
Glue: Industrial contact adhesive
Formal Submittal Sheets Available
Model A8200 is designed for use on:
Intended for Installation on:
Temperature Range:
Pipe Size | Maximum Load Rating (lb.) | A | B | C | Max. Axial Travel (inches) on Pipe Roll +/- |
On Pipe Roll | |||||
6 | 900 | 12 | 9 | 1/2 | 3 |
8 | 1125 | 12 | 9 | 1/2 | 3 |
10 | 1375 | 12 | 9 | 5/8 | 3 |
12 | 2550 | 12 | 9 | 5/8 | 3 |
14 | 2650 | 12 | 9 | 5/8 | 3 |
16 | 2950 | 12 | 9 | 3/4 | 3 |
18 | 3200 | 12 | 9 | 3/4 | 3 |
20 | 3375 | 12 | 9 | 3/4 | 3 |
24 | 3675 | 12 | 9 | 1 | 3 |
30 | 4050 | 12 | 9 | 1 | 3 |
36 | 4050 | 12 | 9 | 1 | 3 |
42 | 4050 | 12 | 9 | 1 | 3 |
TABLE I |