Insulated Pipe Support – Regular Duty with Extended Insulation – A2000

INSULATED PIPE SUPPORT - REGULAR DUTY WITH EXTENDED INSULATION - A2000 - DETAILS

REQUEST A QUOTE



General Dimensions & Specifications

Download PDF

Hardware Sold Separately – Note: For higher load ratings, see A4000, A9000. The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice.

To develop maximum load rating, width of support surface should be at least 1/2 of dimension “A” in Table II. To develop maximum load rating, use band, ring or clevis hanger with manufacturer’s load rating equal to or greater than values shown in Table I.

To obtain load ratings for operating temperatures of 500°F and higher, multiply load rating by factor “F” in Table III.

  • Compact
  • Easy Installation
  • Eliminates welding to pipe
  • Overlapping galvanized sheet metal jacket
  • Minimizes heat loss and/or condensation
  • Calcium silicate insulation extends 1″ beyond the galvanized sheet metal jacket providing for an easier vapor barrier joint with the pipe insulation
  • Copper tubing sizes available
  • Other I.D.’s and/or O.D.’s available on request
  • Clamps available (see G-Series)

Performance Test Results on File: Available upon request.

  • A2000: Applicable PSI spec. doc.: No. 205
  • Insulation: Calcium Silicate asbestos-free, treated with water repellant.
  • Jackets: Galvanized Steel ASTMA-527
  • Glue: Industrial contact adhesive

Formal Submittal Sheets Available

Model A2000 is designed for use on:

  • Cold Water
  • Chilled Water

Intended for Installation on:

  • Flat Surfaces
  • Band, ring or clevis pipe hanger

Temperature Range:

  • Standard: +40°F to +1200°F CalSil Insulation
    Note: Up to 1800°F available upon request.
  • Cryogenic: -275°F to +275°F Urethane Insulation.
    Add U after the model number (i.e., A2000U)
Pipe SizeMaximum Load Rating (lb.)
On Flat Surface (a) (c)In Clevis Hanger (b) (c)
1/23540
3/44045
16065
1 1/47080
1 1/2100110
2125140
2 1/2150200
3180250
3 1/2225300
4270350
5350450
6400550
8450750
105001000
125501200
145751400
166001600
186251800
206752000
247502300
TABLE I
Iron Pipe SizeInsulation ThicknessCopper Tubing Size O.D.
1/23/411 1/222 1/233 1/24
ABABABABABABABABAB
1/2 - 1 1/26246246246246246246246246245/8 - 1 5/8
26246246246246246246246246242 1/8
2 1/2 - 46206206206206206209209209202 5/8 - 4 1/8
56206206206209209209205 1/8
6 - 76206206206209169169166 1/8
8 - 109169169169169169168 1/8 - 10 1/8
12 - 1812161216121612161216121612 1/8
20 - 24181618161816181618161816
TABLE II "B" = gauge of sheet metal jacket
Oper. Temp°FMult. Factor "F"
5000.9
7500.75
10000.5
12000.3
Table III